REQUEST A QUOTE

Panelboard sizing guide

What Information Is Needed to Size a Panelboard?

Panelboard sizing starts with verified system data and an engineered load schedule—not simply the number of circuits. Gather electrical supply, load, fault-current, enclosure, and future-capacity requirements for review.

POWER DISTRIBUTIONBUILT WITH PURPOSE
Close view of an electrical switchgear enclosure and its circuit breakers
Equipment photograph supplied for illustration.
THE DETAILS MATTERMade for the
work ahead.
MADE IN USAAmerican manufacturing
UL 891Switchboard standard reference

UL 891 is a switchboard standard, not a claim of certification. Confirm applicability and listing for each assembly.

01 / PROJECT INPUTS

The right details make the difference.

Start with the requirements that shape your equipment. Share what you know, and identify what needs discussion.

Discuss your project
PROJECT SPECIFICATIONSREFERENCE / 01
Information to share about your switchgear project
DetailWhat to share
EquipmentType of switchgear or distribution equipment needed
ElectricalRequired voltage, current, and fault-duty criteria
ConfigurationInstallation environment, space, and access requirements
DocumentationDrawings, schedules, applicable standards, and desired listings

Requirements and applicable listings depend on the specific project and equipment.

Start with the electrical system and project scope

To size a panelboard, the responsible electrical engineer needs to know what the board will serve and how it connects to the distribution system. Provide the project location within the facility, the intended use, and whether this is a new installation, an expansion, or a replacement design. Identify the upstream source and provide the available one-line diagram or other current system documentation.

Confirm the system voltage, phase, frequency, and grounding arrangement from project records. State whether the panelboard is intended for a particular application or installation environment, and identify any project specifications that govern construction or documentation. Do not infer these characteristics from a building name or a similar panel elsewhere; the engineer must verify the actual electrical system and applicable requirements.

Provide an engineered load schedule

The load schedule is central to determining the required continuous current rating and arrangement. List each connected load, its electrical characteristics, and the branch-circuit protection or connection requirements specified by the design. Include motor loads, heating equipment, receptacle or lighting circuits, and other significant loads where applicable. The engineer must determine the appropriate demand and load calculations rather than simply adding nameplate values or choosing a rating by rule of thumb.

For each load, identify the voltage and phase, expected operating conditions, and whether the load is continuous or intermittent as established by the project design. Flag equipment with starting, inrush, or other operating characteristics that may affect circuit selection. If the load schedule is preliminary, label assumptions clearly and identify information still pending. A manufacturer can work from a defined specification, but cannot responsibly settle unknown building loads on the buyer’s behalf.

Define circuit count, poles and future capacity

Provide the number and type of branch circuits required, including pole count and any special circuit or termination needs identified by the design team. Distinguish circuits required at initial occupancy from positions intended for future use. Clarify whether future capacity means empty spaces, provisions for additional equipment, or an allowance in the calculated load; these are different design choices and should not be treated as interchangeable.

Consider an illustrative small commercial project with a documented supply and an initial schedule of lighting, receptacle and mechanical loads. If the owner expects later equipment additions, the engineer should identify which loads are known, which are forecasts, and how much physical circuit space the design should reserve. The panelboard configuration then follows the verified supply, calculated demand and circuit schedule—not a vague request for a percentage of spare capacity.

Establish available fault current and protection

Panelboard selection also depends on the available fault current at its installation point and the protective devices specified for the system. Provide the latest project fault-current study or the source information the engineer needs to determine the value. Include relevant upstream equipment and conductor details where available; a value from another location may not represent conditions at this panelboard. The responsible engineer must establish the applicable design basis.

Ask the engineer to confirm the required short-circuit rating and the relationship between the panelboard and upstream overcurrent protection. Do not assume that a higher continuous current rating automatically provides an adequate short-circuit rating, or that a protective-device combination is acceptable without design verification. Final ratings, device options and any assembly-specific conditions must be checked against the actual equipment specification.

Specify the enclosure and installation conditions

Describe where and how the panelboard will be installed. Provide available space, mounting arrangement, access and working-clearance constraints for the project team to evaluate, along with relevant environmental conditions such as indoor or outdoor placement. Identify any enclosure or construction requirements in the project documents. The appropriate selection depends on the installation and specification; do not choose an enclosure solely by copying a detail from an unrelated location.

Include practical connection information where known, such as the intended cable or conduit entry, conductor material and termination expectations, and any coordination constraints with adjacent equipment. Drawings, room layouts and a one-line diagram can reveal conflicts early. Qualified project personnel should confirm installation details and applicable safety procedures; the panelboard supplier should not be asked to resolve undocumented field conditions by assumption.

Clarify documentation, standards and design responsibility

Send the governing specifications, drawings and any required submittal or labeling expectations with the inquiry. If a project calls for a particular standard or listing, identify it explicitly so applicability can be reviewed for the proposed design. UL 891 applies to eligible low-voltage switchboards, not automatically to panelboards or every assembly; the specific product classification, design and listing must be confirmed rather than presumed.

Ask who will approve the final load calculations, fault-current basis, protective-device coordination and panel schedule. The project engineer of record retains responsibility for design decisions and code application. A manufacturer can review the supplied requirements and confirm what configuration it can provide, but availability, ratings, testing, listing and delivery details depend on the actual order and must be verified.

Prepare a useful request for review

Before requesting a panelboard, assemble the one-line diagram, system voltage and grounding details, completed or clearly marked preliminary load schedule, circuit and pole counts, available fault-current information, enclosure and mounting conditions, and specified future provisions. Add project specifications, drawing references, required documentation, and the name or role of the person responsible for engineering approval. Note open questions instead of filling gaps with guesses.

Then ask whether the proposed continuous current rating, circuit arrangement, short-circuit rating, enclosure and connection details align with the project documents. Request confirmation of any unresolved design assumptions and the information needed to finalize the configuration. A complete, consistent package helps the manufacturer evaluate a new panelboard against the intended application and gives the engineering team a clear basis for completing and approving the design.

03 / START A CONVERSATION

Let’s talk about your project.

Tell us what you’re working on and the details you have so far. You can include drawings and other documents in your email.

Prefer to call? (951) 403-5738

Email sales: saleselectricalbuyers@gmail.com

PROJECT INQUIRY01 — 04

* Required fields. This form opens your email application; send the prepared message there, or email us directly. You can also call (951) 403-5738.